TDUB Series
The TDUB Series combines digital timing circuitry with universal voltage operation. Voltages of 24 to 240VAC and 12 to 24VDC are available in three ranges. The TDUB Series offers DIP switch selectable time delays ranging from 0.1 seconds to 102.3 minutes in three ranges. Its 1A rated output, ability to operate on multiple voltages, and wide range of switch selectable time delays make the TDUB Series an excellent choice for process control systems and OEM equipment.
Operation (Delay-on-Break):
Input voltage must be applied before and during timing. Upon closure of the initiate switch, the output energizes. The time delay begins when the initiate switch is opened (trailing edge triggered). The output remains energized during timing. At the end of the time delay, the output de-energizes. The output will energize if the initiate switch is closed when input voltage is applied.
Reset: Reclosing the initiate switch during timing resets the time delay. Loss of input voltage resets the time delay and output.
Features:
- Switch selectable time setting
- 0.1s - 102.3m in 3 ranges
- ± 0.5% repeat accuracy
- ± 2% setting accuracy
- 1A, solid-state output
- Wide voltage ranges
Auxiliary Products:
- Female quick connect:
- P/N: P1015-13 (AWG 10/12)
- P/N: P1015-64 (AWG 14/16)
- P/N: P1015-14 (AWG 18/22)
- Quick connect to screw adaptor:
P/N: P1015-18
- DIN rail: P/N: C103PM
- DIN rail adaptor: P/N: 1023-20
|
|